Skip to content

Schneider Electric - Compact Moulded Case Circuit Breaker — fire risk

UK OPSSHigh riskFireAug 14, 2023
Photo from the official notice: Schneider Electric - Compact Moulded Case Circuit Breaker — fire risk

Photos from the official notice: UK Office for Product Safety and Standards (GOV.UK) · image rights

Hazard

The moulded case circuit breakers (MCCB) within the scope of the corrective action have been identified as presenting a risk of overheating, potentially resulting in fire, the production of smoke, or arc flash in rare circumstances. The affected MCCBs may contain a non-conforming component, which may result in the circuit breaker not operating as intended under certain conditions. A short circuit on the electrical downstream network will not trigger the safety protection of the MCCB because of this non-conforming component. Consequently, high current will flow in the load, cable and MCCB, which may lead to fire and smoke depending on the size of the installation and of the short-circuit level. The moulded case circuit breakers within the scope of the corrective action do not meet the requirements of the Electrical Equipment (Safety) Regulations 2016.

Remedy

Schneider Electric has taken the following corrective measures: Notified all direct customers of the risk associated with the potentially affected MCCBs. Ensured third parties or end users have been notified. Offered to replace on site the potentially non-conforming component or replace the MCCB. Provided safety instructions for any intervention, including product date code identification. Provided a warning label informing users of the hazards and that product requires remediation.

Product safety report

Measures taken

  • Warning consumers of risks

Product description

Electrical protection device that is used to protect an electrical circuit from excessive current, which can cause overload or short-circuit.

What should I do?

If you own this product, stop using it and follow the corrective action above: contact the retailer or supplier for a repair, replacement or refund. This notice was published by the UK Office for Product Safety and Standards.