Hazard

The product has been identified by the manufacturer as presenting a risk of as the sand sealing cap may not seal correctly, which could cause the sand to leak during use in high-vibration environments. This can negatively influence the extinguishing behaviour of the fuse in the event of a short circuit. The product does not meet the requirements of the General Product Safety Regulations (2005).

Remedy

The product has been recalled from end users by the manufacturer. Owners should stop using the product immediately and contact Europa’s customer service team to arrange for a return to be made. Europa can be contacted at: Telephone: 01582 692 448 Email: [email protected]

Product recall

Measures taken

  • Recall of product from end users

Product description

Metal electrical fuse link. Manufacture date March 2024-July 2024. Affected fuses can be identified by the production period, either by the calendar weeks on the label on the packaging (032024 to 112024) and/or the quarterly imprint on the fuse: 124=quarter 1 / 2024.

What should I do?

If you own this product, stop using it and follow the corrective action above: contact the retailer or supplier for a repair, replacement or refund. This notice was published by the UK Office for Product Safety and Standards.