Hazard

Hilti (GB) Limited have identified that, due to a manufacturing fault, the active component of the CFS-VB ventilated cavity barrier might not be properly attached. The staples used to fix the intumescent strip in place to the mineral wool component of the cavity barrier may not be of the required number. This may lead to partial detachment of the intumescent strip in the case of fire, potentially reducing the final fire performance of the cavity barrier.

Remedy

Hilti (GB) Limited have issued a recall for a limited number of specific product codes and ranges of ventilated cavity barriers. Affected projects have been notified of the issue directly. Hilti (GB) Limited’s team can be contacted on 0800 886 100 or [email protected] for project managers with questions or requiring assistance.

Product recall

Measures taken

  • Recall of product from end users

Product description

Ventilated cavity barrier comprised of a mineral wool slab, intumescent strip(s) and GF reinforced PE foil.

What should I do?

If you own this product, stop using it and follow the corrective action above: contact the retailer or supplier for a repair, replacement or refund. This notice was published by the UK Office for Product Safety and Standards.