Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

Photos from the official notice: U.S. Consumer Product Safety Commission · image rights
Hazard
On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.
Remedy
All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.
New Instructions
Incidents & injuries
None reported.
Product description
The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.
Sold on
Authorized distributors and installers nationwide from May 2009 through October 2011 for about $1,200.
Contact the company
For more information, contact Bosch Security Systems at (800) 289-0096 between 8:00 a.m. and 8:00 p.m. ET or visit service/customer care on the firm's website at http://www.boschsecurity.us/en-us/ for instructions on how to download software to update the control panels or otherwise address the problems.
What should I do?
Stop using the product and follow the remedy below. Contact the company for a refund, repair or replacement — recall remedies are free.
More from this brand
- Bosch Security Systems Recalls Wireless Smoke Alarms Due to Failure to Alert Consumers to a Fire (Recall Alert)U.S. CPSCSep 9, 2015· Bosch Security Systems· Electrical appliances and equipment
- Bosch Security Systems Recalls Fire Control Panels Due to Fire Alarm Failure (Recall Alert)U.S. CPSCJan 16, 2014· Bosch Security Systems· Electrical appliances and equipment
Recent alerts in this category
- Innovagoods Fotmassageapparat massager — environment riskEU Safety GateSeriousOct 23, 2026· Innovagoods· Electrical appliances and equipment
- Leg and arm moylding massage instrument calf massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Electric Neck Massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Jancheng Electric Neck Massage Tool neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Jancheng· Electrical appliances and equipment
- Massager cervical Vertebra neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Elektrisk nagelfil nail file — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment