CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems

Photos from the official notice: U.S. Consumer Product Safety Commission · image rights
Hazard
One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.
Remedy
Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.
Incidents & injuries
None reported.
Product description
The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit's model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.
Contact the company
For assistance in locating a local independent dealer, contact Trane at (800) 940-1344 between 7:30 a.m. and 4:30 p.m. CT Monday through Friday, or visit the firm's web site at www.trane.com
What should I do?
Stop using the product and follow the remedy below. Contact the company for a refund, repair or replacement — recall remedies are free.
More from this brand
- Trane Recalls Gas/Electric Packaged Units Due to Risk of Gas Leak, Fire HazardU.S. CPSCJul 3, 2025· Trane· Heating and gas appliances
- Trane Recalls Furnaces Due to Shock Hazard (Recall Alert)U.S. CPSCNov 8, 2016· Trane· Heating and gas appliances
- Trane and American Standard Recall Accessory Heaters Due to Fire Hazard (Recall Alert)U.S. CPSCAug 14, 2015· Trane· Heating and gas appliances
- Trane Recalls Air Conditioning Systems Due to Shock Hazard (Recall Alert)U.S. CPSCJun 24, 2014· Trane· Electrical appliances and equipment
- Trane CleanEffects™ and American Standard AccuClean™ Air Filtration Systems Recalled Due to Fire HazardU.S. CPSCAug 3, 2007· Trane· Chemical products
- Trane Recalls Air Conditioners after Incidents of Units SmokingU.S. CPSCNov 30, 2006· Trane· Electrical appliances and equipment
Recent alerts in this category
- Innovagoods Fotmassageapparat massager — environment riskEU Safety GateSeriousOct 23, 2026· Innovagoods· Electrical appliances and equipment
- Leg and arm moylding massage instrument calf massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Electric Neck Massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Jancheng Electric Neck Massage Tool neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Jancheng· Electrical appliances and equipment
- Massager cervical Vertebra neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Elektrisk nagelfil nail file — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment