CPSC, AnnounceGE Security Inc. Retrofit/Recall of Smoke Detector Systems



Photos from the official notice: U.S. Consumer Product Safety Commission · image rights
Hazard
The smoke alarms can fail to activate during a fire or emergency, if installed in combination with certain control panels.
Remedy
Consumers should contact their system installer or service provider to arrange for a free repair or replacement to make the smoke detectors and control panel systems compatible.
Incidents & injuries
None reported.
Product description
The recalled smoke detection systems involve hard-wired S10A ESL smoke detectors that are incompatible with certain ITI control panels as well as certain S09A/S10A listed ESL smoke detectors that may be incompatible with control panels from other manufacturers. Model numbers are printed on the back of the smoke detectors. Inside the ITI control panel is a label that lists the name and model number of the unit. The following model names and model numbers of ITI control panels are incompatible when installed with the following model numbers of ESL smoke detectors: Smoke Detector Model Numbers 429C 429CT 511C 521B (when SW1 is OFF) 521BXT (when SW1 is OFF) 521NB* 521NBXT* 521NCSXT 711U 711UT 721U 721UT *In addition, the models 521NB and 521NBXT detectors, if installed in the S09A configuration, may self-adjust to an S10A configuration. Thus, these two model detectors may not be compatible with other manufacturer's control panels that are only S09A compatible. ITI Control Panel Model Names and Model Numbers Concord: 60-734-01 60-801 60-801-01 60-792-01-95R-16Z 60-792-01-95R-32Z 60-792-95R-32Z Advent: 60-562 (-01 through -06) Concord Express: 60-806-95R-16Z 60-806-95R
Sold on
Distributors, dealers and installers of security systems nationwide, from June 2002 through October 2004. The smoke detectors and the control panels were sold separately as individual components, and were also sold together as part of a security system for between $180 and $1,150.
Contact the company
Call UTC Fire and Security (formerly GE Security) at 855-286-8889 option 2 between 8am and 8pm ET Monday through Friday.
What should I do?
Stop using the product and follow the remedy below. Contact the company for a refund, repair or replacement — recall remedies are free.
More from this brand
- CPSC, GE Security, Inc. Announce Recall of Carbon Monoxide AlarmsU.S. CPSCFeb 12, 2004· GE Security· Electrical appliances and equipment
Recent alerts in this category
- Innovagoods Fotmassageapparat massager — environment riskEU Safety GateSeriousOct 23, 2026· Innovagoods· Electrical appliances and equipment
- Leg and arm moylding massage instrument calf massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Electric Neck Massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Jancheng Electric Neck Massage Tool neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Jancheng· Electrical appliances and equipment
- Massager cervical Vertebra neck massager — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment
- Elektrisk nagelfil nail file — environment riskEU Safety GateSeriousOct 23, 2026· Electrical appliances and equipment