Recalled MA/MH circuit breaker
Recalled MA/MH circuit breaker

Photos from the official notice: U.S. Consumer Product Safety Commission · image rights

Hazard

The circuit breakers may have an incorrect torque load applied to the lug mounting screws. This could cause the clamping load between the lug and the circuit breaker terminals to be lower than specified, resulting in a high temperature condition. Products could overheat causing a fire hazard.

Remedy

Contact Square D for a free repair. Repairs will consist of verifying proper screw torque and tightening all screws that do not meet the required torque specifications.

Incidents & injuries

None reported.

Product description

This recall involves MA/MH circuit breakers manufactured between October 2000 and March 2002.

Sold on

The circuit breakers were sold between October 2000 and March 2002 for between $3,000 and $9,000.

Contact the company

For more information, call (800) 634-8730 between 8 a.m. and 4 p.m. PT Monday through Friday.

What should I do?

Stop using the product and follow the remedy below. Contact the company for a refund, repair or replacement — recall remedies are free.